detcon inc.DetconModel 1212-N4XNEMA 4 Control EnclosureOperator’s Installation & Instruction ManualJanuary 1, 1999 Document #2116 Rev. 1.1ALARM
Table of Contents1.0 Introduction1.1 Description1.2 Specifications1.3 Multiple Alarm Relay Circuit1.4 Alarm Disable1.5 Remote Alarm Reset1.6 Installat
1.2 SPECIFICATIONSElectrical ClassificationNEMA 4XDimensions20.25''W x 20.19''H x 10.25''DCapacity12 single channelsPow
Model 1212-N4X NEMA 4 Control Enclosure PG.4Multiple Alarm Relay CircuitJ1 J2 J3 J4F1 F2 F3 F44321I/OCNCNO4CNCNO3CNCNO2CNC1NOCoil #4Coil #3Coil #2C
Model 1212-N4X NEMA 4 Control Enclosure PG.5Alm PwrAlm ResetVDC INVAC INL1NGNDA (+)B (—)ShldL1NGNDAlm Coil PwrVDCVDCVACmASensorNO/NCComAlm 3NO/NCCo
1.4 ALARM DISABLEThe alarm disable switch, located on the front panel (figure 3), operates by removing DC common from the“Alarm Coil Power” terminals
1.6 INSTALLATION1. Securely mount the 1212-N4X enclosure in accordance with the drawing in figure 5.Note: Reference figure 6 for wiring terminations.
8. If applicable, connect a normally open momentary remote mounted switch to the terminal strip labeled “Alarm Reset”.1.7 START UPUpon completion of
1.9 SPARE PARTS LISTPart # Description5026 Multiple alarm relay circuit0295 5 amp micro fuse3622 250 watt, 24 VDC switcher power supply0224 Gold plat