1.4 INSTALLATION
1. Securely mount the 812B enclosure in accordance with the drawing in figure 1.
NNoottee::
Reference figure 2 for wiring terminations.
2. Connect 117VAC input to the terminal strip labeled “VAC IN” (L1, N, GND).
3. If applicable, connect a 24VDC source or standby battery to the terminal strip labeled “VDC IN” (+ and
–
).
4. Refer to installation and wiring detail of remote mount sensor assemblies as detailed in section 3.0. Terminate
field wiring from sensors to the 812B motherboard. Terminals are labeled “SENSOR” (MA, + and —).
5. If applicable, terminate the discrete 4-20 mA outputs to external device(s). Terminals are labeled “4-20 mA OUT”
(+ and —).
6. If applicable, terminate the RS-485 serial output to external device(s). Terminals are labeled “RS-485” (A+, B–,
and Shield).
Model 812B Rack Mount Control Enclosure PG.4